How to Wire a LX Unit to an external On/Off Controller

Interconnecting wiring between a LX Warm Air Unit to an External On/Off Controller

WARNINGS:

WARNING: The next section must be carried out by a qualified person to current IEE regulations for Electrical Installations and any local regulations which apply.

Warning: The mains electrical supply to the external control should be taken from the appliance terminals t10, t11 and t12 and through a local isolator fitted adjacent to the control.

WARNING: We strongly recommend the use of a suitable screened cable for the 2-core 0-10vdc modulation input on terminals t8/t9.

WARNING: Any sensor wiring MUST BE RUN SEPARATELY and apart from ALL other wiring. Under no circumstances must voltage be applied to the sensor connections.

  Note: Burner Reset terminal is internally connected to NEUTRAL when the reset button is pressed.


Procedure

Mains supply and control circuit wiring should be completed in cables not less than 0.5mm².


Interconnecting wiring diagram LX to an External On/Off Controller